Transmission and Distribution MCQ Quiz - Objective Question with Answer for Transmission and Distribution - Download Free PDF
Last updated on May 8, 2025
Latest Transmission and Distribution MCQ Objective Questions
Transmission and Distribution Question 1:
Why is a radial layout with high voltage drop unsuitable for industrial loads?
Answer (Detailed Solution Below)
Transmission and Distribution Question 1 Detailed Solution
Radial distribution system
- A radial distribution system is a type of electrical power distribution system where each consumer is connected to a single power source or feeder.
- This configuration is simple and cost-effective, but it has a disadvantage in terms of reliability, as a fault in the feeder can result in loss of power to all connected consumers.
Radial layout with high voltage drop is unsuitable for industrial loads because:
- Radial layouts can experience significant voltage drops at points farther from the source, especially under high load conditions.
- Industrial loads (like motors, PLCs, automation systems) are sensitive to voltage variations—fluctuations can cause inefficiencies, overheating, or even equipment malfunction.
- Therefore, radial systems with high voltage drops are not preferred for such loads; more reliable layouts like ring or mesh systems are often used instead.
Transmission and Distribution Question 2:
A 3-phase, 10 kV distribution line delivers power to a load at a 0.8 power factor lagging. If the current is 50 A, and the load resistance and reactance per km are 0.15 Ω and 0.2 Ω, respectively, for a 400 m line, what is the approximate voltage drop per phase (in V/phase)?
Answer (Detailed Solution Below)
Transmission and Distribution Question 2 Detailed Solution
Concept
The voltage drop per phase (in V/phase) is given by:
V = I × ZT
where, V = Voltage drop
I = Current
ZT = Total Impedance
Calculation
Given, cosϕ = 0.8 lag → ϕ = 36.86°
I = 50∠-36.86°
Length = 400 m = 0.4 km
ZT = (0.15 + j0.2) × 0.4
ZT = (0.06 + j0.08) Ω/km
V = (50∠-36.86°) × (0.06 + j0.08)
V = 50(0.8 - j0.6) × (0.06 + j0.08)
V = (40 - j30) × (0.06 + j0.08)
V = 4.8 + j1.4
Transmission and Distribution Question 3:
Which transmission voltage level is commonly used for bulk power transmission over medium distances?
Answer (Detailed Solution Below)
Transmission and Distribution Question 3 Detailed Solution
Concept:
Bulk power transmission requires voltage levels high enough to reduce current and therefore minimize I²R losses and improve efficiency over long conductors.
The classification of voltage levels is:
- Low Voltage (LV): Up to 1 kV
- Medium Voltage (MV): 1 kV to 33 kV – used in distribution networks
- High Voltage (HV): 33 kV to 220 kV – commonly used for bulk power transmission over medium distances
- Ultra-High Voltage (UHV): Above 765 kV – used for long-distance, high-capacity transmission
Final Answer: High Voltage (HV)
Transmission and Distribution Question 4:
Why is voltage drop analysis important in an AC distribution system?
Answer (Detailed Solution Below)
Transmission and Distribution Question 4 Detailed Solution
Explanation
- Voltage drop analysis helps ensure the end-user receives the correct voltage needed for safe and reliable operation of electrical devices.
- Regulatory standards typically specify that the voltage at a user’s point of connection should not deviate more than ±5% for most systems (e.g., from 230V nominal, the range would be 218.5V to 241.5V).
- Excessive voltage drop can cause equipment malfunction or failure. Therefore, analyzing and minimizing voltage drop helps maintain power quality and protect end-user equipment.
- Also, engineers can size conductors correctly, reduce losses, and maintain voltage within this acceptable range.
Transmission and Distribution Question 5:
Which underground cable laying method requires re-excavation for load expansion, making modifications costly?
Answer (Detailed Solution Below)
Transmission and Distribution Question 5 Detailed Solution
Methods of laying underground cables
Direct Laying:
- This method requires digging a 1.5m deep and 0.45m wide trench, which is then covered with sand.
- The cables are laid in the trench and covered with a 10 cm-thick layer of sand. To protect against mechanical injury, the trench is then covered with bricks and other materials.
- If more than one cable is required to be laid in a trench, then a horizontal or vertical inter-axial spacing of 30 cm is provided to prevent mutual heating.
- Direct Laying (Direct Buried Method) requires re-excavation when load expansion or modification is needed, making it costly and labor-intensive.
Draw in the system:
- Ducts or conduits of cast iron or concrete or glazed stone with manholes are placed at suitable locations along the cable route. The manholes are used for pulling the cable in position.
Troughing System:
- A troughing system, also known as a cable troughing system or cable raceway, is a specialized system designed to protect, organize, and route electrical cables within a defined pathway.
- Cables are laid in pre-cast concrete or fiberglass troughs which are then covered.
Solid system:
- Underground cables are laid in open pipes or troughs along the cable route. The troughs are usually made of asphalt, stoneware or cast iron.
- Asphaltic compound is used for filling the troughs once the cable is laid in position.
Top Transmission and Distribution MCQ Objective Questions
The minimum clearance distance that equipment should be kept away from 50 kV power lines is:
Answer (Detailed Solution Below)
Transmission and Distribution Question 6 Detailed Solution
Download Solution PDFThe minimum clearance distance that equipment should be kept away from power lines of different voltage levels is shown in below table.
Voltage |
Minimum clearance distance (feet) |
Up to 50 kV |
10 |
50 to 200 kV |
15 |
200 to 350 kV |
20 |
350 to 500 kV |
25 |
500 to 750 kV |
35 |
750 to 1000 kV |
45 |
Over 1000 kV |
50 |
Which of the following voltage range is used in medium transmission lines?
Answer (Detailed Solution Below)
Transmission and Distribution Question 7 Detailed Solution
Download Solution PDFTransmission lines are classified based on three criteria.
a) Length of transmission line
b) Operating voltage
c) Effect of capacitance
The table below summarizes the classification of transmission lines.
Transmission Lines |
Length of transmission line |
Operating voltage |
Effect of capacitance |
Short transmission line |
(0 - 80) km |
(0 - 20) kV |
'C' is not considered |
Medium transmission line |
(80 - 200) km |
(20 - 100) kV |
'C' is lumped. |
Long transmission line |
(> 200) km |
(> 100) kV |
'C' is distributed |
Which among the following cable are generally suited for the voltage up to 11 kV?
Answer (Detailed Solution Below)
Transmission and Distribution Question 8 Detailed Solution
Download Solution PDFThe following types of cables are generally used for 3-phase service:
1. Belted cables - up to 11 kV
2. Screened cables - from 22 kV to 66 kV
3. Pressure cables - beyond 66 kV
Belted cables:
- These cables are used for voltages up to 11 kV but in extraordinary cases, their use may be extended up to 22 kV
- The belted type construction is suitable only for low and medium voltages as the electrostatic stresses developed in the cables for these voltages are more or less radial i.e., across the insulation
- For high voltages (beyond 22 kV), the tangential stresses also become important
- These stresses act along the layers of paper insulation
- As the insulation resistance of paper is quite small along the layers, therefore, tangential stresses set up leakage current along the layers of paper insulation
- The leakage current causes local heating, resulting in the risk of breakdown of insulation at any moment
Dielectric strength of rubber is around
Answer (Detailed Solution Below)
Transmission and Distribution Question 9 Detailed Solution
Download Solution PDFDielectric Strength:
It reflects the electric strength of insulating materials at various power frequencies.
It is the voltage per unit thickness at which a material will conduct electricity.
Material |
Dielectric Strength (kV/mm) |
Air |
3 |
Oil |
5-20 |
Rubber |
30-40 |
Mica |
118 |
Alumina |
13.4 |
Diamond |
2000 |
A single-phase motor takes 50 A at a power factor angle of 30° lagging from a 250-V, 50-Hz AC supply. What value of capacitance must a shunting capacitor have to raise the power factor to unity?
Answer (Detailed Solution Below)
Transmission and Distribution Question 10 Detailed Solution
Download Solution PDFConcept:
Real power for single-phase P = VI cosθ
Reactive power for single-phase Q = VI sinθ
For purely capacitive circuit Q = v2ω c
Note: To suppress the inductive effect of load, we add purely capacitive load across load.
Calculation:
Given V = 250 volt
I = 50 amp
θ = 30°
ω = 2 × π × 50 = 314
Reactive power = 250 × 50 × sin30° = 6250 VAr
For unity power factor, we add capacitance across load
V2ωC = 6250 VAr
⇒ 2502 × 314 × C = 6250 VAr
⇒ C = 318.3 μFIn the case of three core flexible cable the colour of the neutral is
Answer (Detailed Solution Below)
Transmission and Distribution Question 11 Detailed Solution
Download Solution PDFConcept:
Function |
Colour code |
Single-phase line |
Red/Brown |
Single-phase neutral |
Black/Blue |
Ground wire |
Green |
Three-phase line 1 |
Red |
Three-phase line 2 |
Yellow |
Three-phase line 3 |
Blue |
Three-phase neutral |
Black |
Three-phase protective ground or earth |
Green (or) Green - Yellow |
Neutral wire (3-core flexible cable) | Blue |
The skin effect does not depend upon:
Answer (Detailed Solution Below)
Transmission and Distribution Question 12 Detailed Solution
Download Solution PDF- The phenomenon arising due to unequal distribution of current over the entire cross-section of the conductor is referred to as the skin effect.
- Such a phenomenon does not have much role to play in case of a very short transmission line, but with an increase in the effective length of the conductors, skin effect increases considerably.
- The distribution of current over the entire cross-section of the conductor is quite uniform in the case of a DC system.
- But in the alternating current system, current tends to flow with higher density through the surface of the conductors (i.e., the skin of the conductor), leaving the core deprived of current.
The cross-sectional area of a round conductor available for conducting DC current. (DC resistance) |
|
|
The cross-sectional area of the same conductor available for conducting low-frequency AC (AC resistance) |
|
The cross-sectional area of the same conductor available for conducting high-frequency AC (AC resistance) |
Factors affecting skin effect in transmission lines are:
- Frequency – The skin effect increases with the increase in frequency.
- Diameter – It increases with the increase in the diameter of the conductor.
- The shape of the conductor – Skin effect is more in the solid conductor and less in the stranded conductor because the surface area of the solid conductor is more.
- Type of material – Skin effect increase with the increase in the permeability of the material (Permeability is the ability of the material to support the formation of the magnetic field).
Important Points:
- The Skin effect is negligible if the frequency is less than the 50Hz and the diameter of the conductor is less than the 1cm.
- In the stranded conductors like ACSR (Aluminium Conductor Steel Reinforced) the current flows mostly in the outer layer made of aluminum, while the steel near the center carries no current and gives high tensile strength to the conductor.
- The concentration of current near the surface enabled the use of an ACSR conductor.
The type of insulator used on lines up to 33 kV is :
I. Pin insulator
II. Reel insulator
III. Post insulator
IV. Strain insulatorAnswer (Detailed Solution Below)
Transmission and Distribution Question 13 Detailed Solution
Download Solution PDF- Pin insulators are used for holding the line conductors on the straight running of poles. These are commonly used in power networks up to 33 kV system.
- Suspension insulators consist of a number of porcelain discs connected in series by metal links in the form of a string. The conductor is suspended at the bottom end of this string while the other end of the string is secured to the cross- arm of the tower. For high voltage (>33KV), it is a usual practice to use suspension type insulators.
- When there is a dead-end of the line or there is a corner or sharp curve, the line is subjected to greater tension. In order to relieve the line of excessive tension, strain insulators are used.
- For low voltage lines (<11 kV) shackle insulators are used as strain insulators.
- Stay insulators are also known as strain insulators and are generally used up to 33 kV line. These insulators should not be fixed below three meters from the ground level. These insulators are also used where the lines are strained.
The current in a transmission line under no load conditions is due to:
Answer (Detailed Solution Below)
Transmission and Distribution Question 14 Detailed Solution
Download Solution PDF- During the no-load condition, the current flowing is only charging current due to line capacitance. It increases the capacitive var in the system.
- Since the line is under no load the line inductance will be less. Therefore, the capacitive var becomes greater than inductive var during no load or light load condition.
- Due to this phenomenon, the receiving end voltage becomes greater than the sending end voltage. This effect is also called the Ferranti effect.
Cables used for underground services from 33 kV to 60 kV are:
Answer (Detailed Solution Below)
Transmission and Distribution Question 15 Detailed Solution
Download Solution PDFClassification of underground cables on the basis of voltage level is given below
Type of Cable |
Voltage level (kV) |
Low tension (L.T.) Cable |
0 – 1 kV |
High tension (H.T.) Cable |
1 – 11 kV |
Super tension (S.T.) Cable |
11 – 33 kV |
Extra high-tension (E.H.T.) Cable |
33 – 66 kV |
Extra super-tension(E.S.T.) Cable |
66 kV and above |