Question
Download Solution PDFA 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative and zero sequence impedances are 0.30, 0.40 and 0.05 pu respectively. What value of reactance must be placed in the generator neutral so that the fault current for a line to ground fault of zero fault impedance shall not exceed the rated line current.
Answer (Detailed Solution Below)
Detailed Solution
Download Solution PDFProblem Statement: A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative, and zero sequence impedances are 0.30 pu, 0.40 pu, and 0.05 pu respectively. We need to determine the value of reactance that must be placed in the generator neutral so that the fault current for a line-to-ground fault of zero fault impedance does not exceed the rated line current.
Solution:
To solve this problem, we will calculate the required reactance step by step:
Step 1: Determine the base current
The base current for the system can be calculated using the formula:
Ibase = (Sbase × 106) / (√3 × Vbase)
Here:
- Sbase = 30 MVA = 30 × 106 VA
- Vbase = 13.2 kV = 13.2 × 103 V
Substituting the values:
Ibase = (30 × 106) / (√3 × 13.2 × 103)
Ibase = 1311.78 A
So, the base current of the system is 1311.78 A.
Step 2: Determine the per unit fault current for a line-to-ground fault
In the case of a line-to-ground fault, the equivalent impedance is given by:
ZLG = Z1 + Z2 + (Z0 || ZN)
Where:
- Z1 = Positive sequence impedance = 0.30 pu
- Z2 = Negative sequence impedance = 0.40 pu
- Z0 = Zero sequence impedance = 0.05 pu
- ZN = Neutral reactance to be determined
The fault current is inversely proportional to the equivalent impedance. The fault current in per unit (If) for a line-to-ground fault can be expressed as:
If = 1 / ZLG
We are tasked with limiting the fault current to the rated line current (i.e., 1 pu). Hence, the equivalent impedance must satisfy:
ZLG = 1 pu
Substituting the values into the equation for ZLG:
1 = 0.30 + 0.40 + (0.05 || ZN)
Step 3: Solve for ZN
The parallel combination of Z0 and ZN is given by:
(0.05 || ZN) = (Z0 × ZN) / (Z0 + ZN)
Substituting this into the equation for ZLG:
1 = 0.30 + 0.40 + [(0.05 × ZN) / (0.05 + ZN)]
Rearranging:
0.30 + 0.40 = 0.70
1 - 0.70 = (0.05 × ZN) / (0.05 + ZN)
0.30 = (0.05 × ZN) / (0.05 + ZN)
Cross-multiplying:
0.30 × (0.05 + ZN) = 0.05 × ZN
Expanding and simplifying:
0.015 + 0.30 × ZN = 0.05 × ZN
0.30 × ZN - 0.05 × ZN = 0.015
0.25 × ZN = 0.015
Solving for ZN:
ZN = 0.015 / 0.25 = 0.06 pu
Step 4: Convert ZN to ohms
To convert the per unit reactance into ohms, we use the base impedance:
Zbase = (Vbase)2 / Sbase
Substituting the values:
Zbase = (13.2 × 103)2 / (30 × 106)
Zbase = 5.808 ohms
Now, the neutral reactance in ohms is:
XN = ZN × Zbase
XN = 0.06 × 5.808
XN = 0.34848 ohms
**Last updated on Jul 1, 2025
-> JKSSB Junior Engineer recruitment exam date 2025 for Civil and Electrical Engineering has been rescheduled on its official website.
-> JKSSB JE exam will be conducted on 31st August (Civil), and on 24th August 2025 (Electrical).
-> JKSSB JE application form correction facility has been started. Candidates can make corrections in the JKSSB recruitment 2025 form from June 23 to 27.
-> JKSSB JE recruitment 2025 notification has been released for Civil Engineering.
-> A total of 508 vacancies has been announced for JKSSB JE Civil Engineering recruitment 2025.
-> JKSSB JE Online Application form will be activated from 18th May 2025 to 16th June 2025
-> Candidates who are preparing for the exam can access the JKSSB JE syllabus PDF from official website of JKSSB.
-> The candidates can check the JKSSB JE Previous Year Papers to understand the difficulty level of the exam.
-> Candidates also attempt the JKSSB JE Mock Test which gives you an experience of the actual exam.